Артикул: Liquiphant FTL62
Производитель: Endress+Hauser
Наличие: Под заказ
Цена:
уточняйте у менеджера
A level switch for aggressive and pumpable liquids Liquiphant FTL62 has a strong focus on specific applications with aggressive liquids and simplicity with easy proof testing, reliability and safety (SIL) with compliance to IEC 61508, API 2350 and WHG. The vibronic device is determined for a safe and active measuring technology in aggressive liquids and want a reliable and proven point level detection for tank overfill prevention and pump dry run protection. The FTL62 is easy to use, has a digital connection and gives a real-time data at hand. Краткие характеристики Liquiphant FTL62Рабочая температура-50 °C...+150 °C(-58 °F...+302 °F)
Рабочее давление абс. / макс. предел избыточного давленияVacuum...40 barVacuum...580 psi
Мин. плотность измеряемого продукта0.5 г/см³(0.4 г/см³, опция)Подробное описание Liquiphant FTL62 Преимущества Universal measuring principle for limit detection – proven vibronic technology
Developed according IEC 61508 for highest safety – SIL2/3 applications (3rd party approved)
Periodic proof testing is quickly and simple organized with guided wizards via the SmartBlue-App or via a test button or magnetic pin from outside. Via these ways, you can initiate the instrument for a fast and easy testing of the safety loop
Heartbeat Technology allows safe, continuous diagnostics and a simple verification
Heartbeat Diagnostics: Permanent diagnostics increase the safety of the plant. You connect your device via the SmartBlue-App and you easily have real time diagnostics at hand
Heartbeat Verification: The device can be verified without process interruption. The verification report is generated automatically
Heartbeat Monitoring: With the frequency tracking of the sensor data you have all information at hand for predictive maintenance and process optimization strategies Область применения
Point level switch with extension tube for pumpable liquids
Coated sensor for aggressive media: ECTFE (Halar), PFA (EdlonTM, Ruby Red, conductive), Enamel
Process temperature: -60 °C to +150°C
Process pressure: -1 to +40bar
Ambient temperature: -60 to +70°C
Viscosity up to 10,000mm2/s (cSt)
Process connections: Threads, flanges and hygienic process connection (Tri-Clamp)
International explosion protection certificates, overfill prevention WHG, SIL, marine approvals
Характеристики и спецификации Контроль предельного уровня/жидкие продукты Принцип измеренияВибрационные датчики, жидкие продукты
Характеристики/ПрименениеCompact vibronic device with highly corrosion-resistant coating for aggressive media,Optional extension tube up to 3 m (9.8ft),Modular housing concept
Доп.информацияHeartbeat Technology,Bluetooth® Operation and maintenance SmartBlue App,LED Module,RFID TAG for easy identification,Second line of defenseTemperature spacer for high process temperature,Plug and play functionalities
Питание / Коммуникация19...253В перем.тока / 2-провод.,10...55В / DC-PNP 3-провод.,9...20В пост. тока с реле DPDT,19...253В перем.тока или 19...55В пост.тока с реле DPDT,2-провод. NAMUR,2-провод. PFM
Температура окружающей среды-60 °C...+70 °C
Рабочая температура-50 °C...+150 °C(-58 °F...+302 °F)
Рабочее давление абс. / макс. предел избыточного давленияVacuum...40 barVacuum...580 psi
Мин. плотность измеряемого продукта0.5 г/см³(0.4 г/см³, опция)
Смачиваемые частиECTFE,PFA (Edlon, RubyRed or conductive)316LEnamel
Присоединение к процессуFlanges:DN25...DN100ASME 1"...4"JIS 50A
Длина датчикаUp to 3 m (9.8ft)
Связь2-провод., прямое управление нагрузкойDC-PNP 3-провод.РелеNAMURPFMБеспроводная технология Bluetooth®
Сертификаты/НормативыATEX, IEC Ex
Сертификаты безопасностиOverfill protection WHGSIL2/ SIL 3 according to IEC 61508
Сертификат по конструкцииEN 10204-3.1ASME B31.3 Process PipingCRN
ОпцииAmbient temperature down to -60 °C (-76 °F),Heavy duty stainless steel housing
КомпонентыFTL325P Interface PFMFTL325N Interface NAMUR